Q1MHT CET 2026 · 13 MAY · SHIFT 2Easy
AC Generator & Transformer · Transformer ratios
A step down transformer has 50 turns on secondary and 1000 turns on primary winding. If a transformer is connected to 220 V and 1 A a.c. source, what is the output current of the transformer?
A transformer has 120 turns in the primary coil and carries 5A current. Input power is one kilowatt. To have 560 V output, the number of turns in secondary coil will be
An ideal transformer converts 220V a.c. to 3.3 KV a.c. to transmit a power of 4.4 KW. If primary coil has 600 turns then alternating current in the secondary coil is
If a transformer of an amplifier has output impedance 8000Ω and the speaker has input impedance of 8Ω, the primary and secondary turns of this transformer connected between the output of amplifier and to loudspeaker should have the ratio
Alternating current of peak value (π2) A flows through the primary coil of a transformer. The coefficient of mutual inductance between primary and secondary coils is 1H. The peak value of induced e.m.f. in the secondary coil is
AC Generator & Transformer · Efficiency and energy losses
A transformer having an efficiency 80% is working on 200 V and 4 kW power supply. If the current in the secondary coil is 5 A, the voltage across the secondary coil and the current in the primary coil, respectively, are
AC Generator & Transformer · Efficiency and energy losses
A current of 5 A is flowing at 220 V in the primary coil of a transformer. If the voltage produced in the secondary coil is 2200 V and 50% of power is lost, then the current in secondary will be
AC Generator & Transformer · Efficiency and energy losses
A transformer having efficiency 90% is working on 200 V and 3 KW power supply. If the current in the secondary coil is 6A, the voltage across the secondary coil and the current in the primary coil, respectively, are
AC Generator & Transformer · Efficiency and energy losses
A current of 4 A is flowing at 230 V in the primary coil of a transformer. If the voltage produced in the secondary coil is 2300 V and 40 % of power is lost, then the current in the secondary will be
An ideal transformer converts 220 a.c. to 3.3 kV a.c. to transmit a power of 4.4 kW. If primary coil has 600 turns then alternating current in secondary coil is
AC Generator & Transformer · Efficiency and energy losses
A current of 5 A is flowing at 220 V in a primary coil of a transformer. If the voltage produced in the secondary coil is 2200 V and 50% of power is lost, then the current in the secondary coil will be
A transformer has 120 turns in the primary coil and carries 5 A current. Input power is one kilowatt. To have 560 V output, the number of turns in secondary coil will be
A transformer is used to set up an alternating e.m.f. of 220 V to 4.4 kV to transmit 6.6 kW of power. The primary coil has 1000 turns. The current rating of the secondary coil is (Transformer is ideal)
A step up transformer is connected to an ac mains supply of 220 V to operate at 11000 V,88 watt. The current in the secondary circuit, ignoring the power loss in the transformer, is
Primary coil of a transformer is connected to 220 V ac. Primary and secondary turns of the transformer are 100 and 10 respectively. Secondary coil of transformer is connected to two series resistances shown in figure. The output voltage (V0) is:
If a transformer of an audio amplifier has output impedance 8000Ω and the speaker has input impedance 8Ω, the primary and secondary turns of this transformer connected between the output of amplifier and to loudspeaker should have the ratio
Alternating current of peak value (π2) A flows through the primary coil of a transformer. The coefficient of mutual inductance between primary and secondary coils is 1 H. The peak e.m.f. induced in secondary coil (Frequency of a.c. =50 Hz)
Primary side of a transformer is connected to 230 V,50 Hz supply. Turns ratio of primary to secondary winding is 10:1. Load resistance connected to secondary side is 46Ω. The power consumed in it is:
AC Generator & Transformer · Efficiency and energy losses
A transformer having efficiency 90% is working on 200 V and 3 kw power supply. If the current in the secondary coil is 6 A, the voltage across the secondary coil and the current in the primary coil are respectively
A power transmission line feeds input power at 2.3 kV to a step down transformer with its primary winding having 3000 turns. The output power is delivered at 230 V by the transformer. The current in the primary of the transformer is 5 A and its efficiency is 90%. The winding of transformer is made of copper. The output current of transformer is _________ A.
Numerical answer type. Work it out, then open the answer.
The coil of an a.c. generator has 100 turns, each of cross-sectional area 2 m2. It is rotating at constant angular speed 30 rad/s, in a uniform magnetic field of 2×10−2 T. If the total resistance of the circuit is 600Ω then maximum power dissipated in the circuit is
In an ac generator, a rectangular coil of 100 turns each having area 14×10−2 m2 is rotated at 360 rev/min about an axis perpendicular to a uniform magnetic field of magnitude 3.0 T. The maximum value of the emf produced will be ________ V.
( Take π=722)
Numerical answer type. Work it out, then open the answer.
The number of turns in the primary and the secondary of a transformer are 1000 and 3000, respectively. If 80 V AC is applied to the primary coil of the transformer, then the potential difference per turn of the secondary coil would be
A 12 V,60 W lamp is connected to the secondary of a step down transformer, whose primary is connected to ac mains of 220 V. Assuming the transformer to be ideal, what is the current in the primary winding?
A square shaped coil of area 70 cm2 having 600 turns rotates in a magnetic field of 0.4 wbm−2, about an axis which is parallel to one of the sides of the coil and perpendicular to the direction of field. If the coil completes 500 revolutions in a minute, the instantaneous emf when the plane of the coil is inclined at 60∘ with the field, will be ____________ V. (Take π=722)
Numerical answer type. Work it out, then open the answer.
An ideal transformer with purely resistive load operates at 12 kV on the primary side. It supplies electrical energy to a number of nearby houses at 120 V. The average rate of energy consumption in the houses served by the transformer is 60 kW. The value of resistive load (Rs) required in the secondary circuit will be ___________ mΩ.
Numerical answer type. Work it out, then open the answer.
A transformer operating at primary voltage 8 kV and secondary voltage 160 V serves a load of 80 kW. Assuming the transformer to be ideal with purely resistive load and working on unity power factor, the loads in the primary and secondary circuit would be
A step up transformer operates on 220 V and supplies current of 2 A. The ratio of primary and secondary windings is 1:20. The current in the primary is
A step down transformer connected to an ac mains supply of 220 V is made to operate at 11 V, 44W lamp. Ignoring power losses in the transformer, what is the current in the primary circuit?
AC Generator & Transformer · Efficiency and energy losses
A step down transformer is used to reduce the main supply from 'V1 ' volt to 'V2 ' volt. The primary coil draws a current 'I1' A and the secondary coil draws 'I2 ' A. (I1<I2). The ratio of input power to output power is
A common transistor radio set requires 12 V (D.C.) for its operation. The D.C. source is constructed by using a transformer and a rectifier circuit, which are operated at 220 V (A.C.) on standard domestic A.C. supply. The number of turns of secondary coil are 24, then the number of turns of primary are ___________.
Numerical answer type. Work it out, then open the answer.
A step-up transformer has 300 turns of primary winding and 450 turns of secondary winding. A primary is connected to 150 V and the current flowing through it is 9A. The current and voltage in the secondary are
AC Generator & Transformer · Efficiency and energy losses
A 220 V input is supplied to a transformer. The output circuit draws a current of 2.0 A at 440 V. If the ratio of output to input power is 0.8, then the current drawn by primary winding is
AC Generator & Transformer · Efficiency and energy losses
A transformer consisting of 300 turns in the primary and 150 turns in the secondary gives output power of 2.2 kW. If the current in the secondary coil is 10A, then the input voltage and current in the primary coil are:
AC Generator & Transformer · Efficiency and energy losses
A power transmission line feeds input power at 2300 V to a step down transformer with its primary windings having 4000 turns. The output power is delivered at 230 V by the transformer. If the current in the primary of the transformer is 5A and its efficiency is 90%, the output current would be:
A power transmission line feeds input power at 2300 V to a step down transformer with its primary windings having 4000 turns, giving the output power at 230 V. If the current in the primary of the transformer is 5 A, and its efficiency is 90%, the output current would be;
AC Generator & Transformer · Efficiency and energy losses
A transformer having efficiency of 90% is working on 200 V and 3 kW power supply. If the current in the secondary coil is 6 A, the voltage across the secondary coil and the current in the primary coil respectively are
The primary of a transformer when connected to a dc battery of 10 Volt draws a current of 1 mA. The number of turns of the primary and secondary windings are 50 and 100 respectively. The voltage in the secondary and the current drawn by the circuit in the secondary are respectively
AC Generator & Transformer · Efficiency and energy losses
A 220 volt input is supplied to a transformer. The output circuit draws a current of 2.0 ampere at 440 volts. If the efficiency of the transformer is 80%, the current drwn by the primary windings of the transformer is
AC Generator & Transformer · Efficiency and energy losses
A transformer is used to light a 100 W and 110 V lamp from a 220 V mains. If the main current is 0.5 amp, the efficiency of the transformer is approximately
The primary and secondary coils of a transformer have 50 and 1500 turns respectively. If the magnetic flux ϕ linked with the primary coil is given by ϕ=ϕ0 + 4t, where ϕ is webers, t is time in seconds and ϕ0 is a constant, the output voltage across the secondary coil is
In an AC generator, a coil with N turns, all of the same area A and total resistance R, rotates with frequency ω in a magnetic field B. The maximum value of emf generated in the coil is
In a transformer, number of turns in the primary coil are 140 and that in the secondary coil are 280. If current in primary coil is 4A, then that in the secondary coil is
A step-up transformer operates on a 230 V line and supplies current of 2 A to a load. The ratio of the primary and secondary windings is 1:25. The current in the primary coil is
The primary winding of a transformer has 500 turns whereas its secondary has 5000 turns. The primary is connected to an A.C. supply 20 V, 50 Hz. The secondary will have an output of
In a region of magnetic induction B=10−2 tesla, a circular coil of radius 30 cm and resistance π2 ohm is rotated about an axis which is perpendicular to the direction of B and which forms a diameter of the coil. If the coil rotates at 200 rpm the amplitude of the alternating current induced in the coil is